AN11-18Application note, page 2 of 6

Transformer considerations with thyristor controls

Introduction: thyristors and transformers

Generally speaking, a transformer is an AC (alternating current) device.

The ordinary thyristor (SCR) is basically a bistable DC device: when it turns on, it allows the source voltage to impress a DC current on the load, and it will not turn off until the current returns to zero for a few microseconds. Because of this, it can be very destructive to transformers, and to itself, when operated incorrectly into transformer loads.

14
Figure 1. AC switch.

By using two thyristors in an inverse-parallel connection, per Fig. 1, it is possible to effectively adjust the primary voltage of the transformer by using “phase-angle control” to vary the primary voltage from 0 to the nominal mains voltage of the system.

This application note addresses three basic modes of transformer operation with thyristor controls:

  1. Mode 1. Transformer connected between the thyristor control and the load.
  2. Mode 2. Small single phase transformers connected to the load side of zero-fired thyristor controls.
  3. Mode 3. Transformer connected before the thyristor control and the load.